UPS 400-230

Range of uninterruptible power supply units

About

The units are designed to ensure uninterruptible power supply for the equipment with operating voltage 230/400 V.

The units may be used as emergency/standby AC power sources 230/400 V 50 Hz for various equipment (including shipborne).

Description

The unit is designed for operation with three-phase four-wire AC network, frequency 50 Hz, voltage 380/400 V (when N is absent, the scope of supply includes transformer 400/400 Δ-Y).

To ensure power redundancy, the unit is powered by two lines (main/standby). Integrated automatic transfer equipment is used for automatic transfer to standby power in the event of power mains failure and vice versa.

In the event of input power failure, the unit automatically switches over to built-in accumulator batteries.

The scope of supply may optionally include a switchboard to power consumers.

Features

  • Main and standby power indication
  • Signal output to alarm warning system (AWS) in the event of faults (dry contact)
  • AB protection against deep discharge, overload and short circuit
  • Automatic power transfer to AB and vice versa in the event of power mains failure

Specifications

  UPS-230-230-10  UPS-400-400-30
Input (main) AC voltage frequency 50 Hz, V 1) 230 400 (360 - 440)
Input (standby) AC voltage frequency 50 Hz, V 1) 230 400 (360 - 440)
Rated output AC voltage frequency 50 Hz, V 1) 230 400
Output phases, pcs.  1 3
Rated output power, kVА  10 kVА  30 kVА
Rated output current, А  <50  <68
Max. rated power consumption, kW  13 38
Min. efficiency, %  85
DC voltage of AB, V  51.2
Number of batteries in battery pack, pcs.  16
Min. voltage of built-in AB, V  44
Type of built-in AB  lithium iron phosphate
AB capacity, А·h  375 840
Min. operation time from AB, minutes 2)  30
Outline dimensions (W х H х D), mm  UPS  1000х2000х670  800х2100х670
Switchboard  400х500х210  500х600х210
AB  –  800х2100х670
Max. weight, kg  UPS  515 780
Switchboard  29 45
AB  –  740
IP rating  UPS  22 22
Switchboard 44 44
AB  –  22
Operating temperature, °С  0 … +55
Limiting temperature, °С   –15 … +70
UPS mounting  wall-attached   wall-attached
Switchboard mounting  hinged  hinged
AB mounting  –  wall-attached
Connected loads, pcs.  230 V  10
400 V  –  18

1) input voltage range.

2) Operating time at rated power.

«–» means that parameter is not available.