RSC 300
Reversible static converter 300 kW
Description
Reversible static converter 300 kW (RSC 300) is designed to charge and discharge energy storage systems. The unit ensures power scaling of several converters (300 kW, 600 kW, 900 kW, 1.2 MW) to use them as a part of charging stations, uninterruptible power supply units or industrial systems of power compensation.
The converter ensures:
- power conversion of three-phase alternating current network, voltage 400 V and frequency 50 Hz, to DC voltage 600 — 900 V to charge energy storage systems (ESS);
- conversion of DC power, voltage 650 — 900 V, from ESS to three-phase power network 400 V 50 Hz;
- synchronization to power network when connecting;
- emergency shutdown in the event of emergency, warning and alarm signaling;
- control of charge/discharge voltage and current;
- transmission of monitored parameters via MODBUS TCP.
A function of power factor correction significantly decreases harmonic distortion of input current. An isolation transformer between RSC and three-phase network 400 V 50 Hz provides additional protection and electromagnetic compatibility.
The converter’s cooling system ensures combined liquid and air cooling by built-in fans.
Main technical specifications of RSC 300
Environmental conditions |
Operating temperature |
-40 … + 45 C |
|
---|---|---|---|
Storage temperature |
-40 … + 75 C |
||
Humidity |
< 90 % w/o condensation |
||
Mode of alternating to direct current conversion |
AC input |
Rated values of voltage and current |
400 V; 3ph.+PE; 0…450 A |
Operating voltage range |
320…440 V |
||
Frequency |
45 … 55 Hz |
||
Power factor |
> 99% at load more than 30 % |
||
Total harmonic distortion (THD) |
< 5 % |
||
AC output |
Max. power |
300 kW |
|
Range of voltage and current values |
650 V … 900 V 0...500 A |
||
Output voltage accuracy |
<2 % |
||
Output current accuracy |
<2 % at load 20 % |
||
Efficiency |
> 95% |
||
Transition time from AC2DC mode to DC2AC (AB testing) |
100 ms |
||
Mode of alternating to direct current conversion |
DC input |
Operating voltage range |
650 V … 900 V |
Max. current |
500 А |
||
AC output |
Output voltage |
320…440 V; 3ph. |
|
Output current |
0…450 A |
||
Max. power |
300 kW |
||
Frequency |
45 … 55 Hz |
||
Total harmonic distortion (THDi) |
< 5 % |
||
Efficiency |
> 95% |
||
Protection |
Input/output voltage over limit |
Automatic shutdown, automatic restart when voltage is normal |
|
Overcurrent or short circuit |
Automatic shutdown, restart is required to restore operation |
||
Overheating |
Automatic shutdown, restart is required to restore operation |
||
Data exchange |
Modbus TCP / (Modbus RTU optionally) |
||
Weight |
450 kg |
||
Outline dimensions (height*width*depth) |
2000х600х755 mm |