Marine UPS

Uninterruptible power supply unit for shipborne AC equipment

About

Uninterruptible power supply unit for shipborne AC equipment with frequency 50 or 60 Hz and voltage from 200 to 240/380 V.

Description

Designed to operate with single-phase AC mains, frequency 50 (60) Hz and voltage 220 V, or three-phase AC mains, frequency 50 (60) Hz and voltage 380 V.

Features

  • Output AC voltage with frequency 50 (60) Hz and rated voltage 200/208/220/230/240/380 V
  • Power for connected load with total power consumption from 0.9 to 10.0 kW in normal operation mode (depending on the type)
  • Accuracy of output voltage ±1 % from the preset voltage
  • Automatic power transfer to AB in the event of power mains failure and vice versa
  • Monitoring of parameters on the LCD
  • Sound and light indication of emergency condition
  • Connection of additional AB to increase battery operation time
  • Protection of output contacts against short circuit, overvoltage and overload

Technical specifications of UPS Marine-1, 2, 3 range

  UPS Marine-1 UPS Marine-2 UPS Marine-3
Rated output power 0.9 kW (kVA) 1.8 kW (kVA) 2.7 kW (kVA)
Max. rated power consumption 1.0 kW 2.0 kW 3.0 kW
Input voltage (AC frequency 50 (60)Hz ± 10Hz, V) 220 (180 - 264)* 1 phase
Output AC voltage, V 200**, 208**, 220, 230, 240 1 phase
Output frequency 50, 60Hz 50, 60Hz 50, 60Hz
Efficiency 90% 90% 90%
Voltage of built-in DC battery 12V 12V 12V
Quantity of built-in batteries 2 4 6
Min. voltage of built-in battery 19.95V 39.9V 59.85V
Type of built-in AB Sealed lead acid
Capacity of built-in battery 9А·h 9А·h 9А·h
Operation time from AB 6.5 min 7.0 min 7.0 min
Battery charge time up to 90% of charge level 3 h 3 h 3 h
Battery charge current 1.5А 2.0А 2.0А
Number of connected loads, pcs (total load current, А, max.) 6 (10) - С13 6 (10) - С13 1 (16) - С19 6 (10) - С13 1 (16) - С19
Connectors USB port type B - 1, RS-232 port - 1, REPO port - 1, connection of external AB - 1
    Overload operation time   up to 105% w/o time limitations
from 105% to 125% 60 sec
from 125% to 150% 15 sec
over 150% Double conversion mode transfer to bypass mode
over 150% AB mode full disconnection
Outline dimensions (WхDхH),mm 440х335х89 440х432х89 440х610х89
Weight**** 16kg 28kg 45kg
Operating temperature,°С***** 0...+50°С 0...+50°С 0...+50°С
Limiting temperature,°С -15...+50°С -15...+50°С -15...+50°С
IP rating IP22
Mounting horizontal

* Input voltage range

** Rated power shall be decreased to 90%

*** Under 75% total load

**** Weight w/o installation kit

***** At operating temperature +40°С...+50°С power decreases up to 80% from the rated

Technical specifications of UPS Marine-5, 6, 8, 10/1, 10/3, 20/3 range

    UPS Marine-5 UPS Marine-6 UPS Marine-8 UPS Marine-10/1 UPS Marine-10/3 UPS Marine-20/3
Rated output power 5.0 (5) kW (kVA) 6.0 (6) kW (kVA) 8.0 (8) kW (kVA) 10.0 (10) kW (kVA) 10.0 (10) kW (kVA) 20.0 (20) kW (kVA)
Type of connected battery lead-acid
Rated power consumption 5.6 kW 6.7 kW   8.9 kW  11.1 kW  11.1 kW  22.2 kW
Max. charge current of connected AB
Number of connected loads 2 (terminal block) 1 (terminal block)
Connectors
  • USB port type B - 1 port
  • RS-232 - 1 port
  • RS-485 - 1 port
  • REPO - 1
  • Connection of AB - 1
  • Dry contacts - 4
  • Parallel connection ports - 2
  • USB port type B - 1 port
  • RS-485 - 1
  • REPO port - 1
  • Connection of AB - 1
  • Dry contacts - 4
  • Ports of parallel connection - 2
Overload operation time max. 105% unlimited time
from 105% to 125% 180.0 s
from 126% to 150%  60.0 s
over 150% 0.5 s
Outline dimensions (H) 440х643х89mm 440х728х89mm 440х760х89mm
Weight** 11.9kg 11.9kg 16.2kg 16.2kg 24.0kg 24.0kg
Operating temperature*** 0...+50°С
Limiting temperature -15...+50°С
IP rating IP22
Mounting horizontal

* Input voltage range

** Weight w/o installation kit

*** At operating temperature +40°С...+50°С product’s power decreases up to 75% of the rated power

AB technical specifications

  AB AG-24 AB AG-48 AB AG-72 AB AG-192 AB AG-240
Voltage of DC battery 24V 48V 72V 192V 240V
Quantity of AB 4 8 12 16 20
Min. voltage of built-in AB 19.95V 39.9V 59.85V 168.00V ± 3% 210.00V ± 3%
Type of AB lead-acid
AB capacity 9А·h 9А·h 9А·h 7А·h 9А·h
Outline dimensions width 440mm 440mm 440mm 440mm 440mm
depth 335mm 435mm 610mm 565mm 650mm
height 89mm 89mm 89mm 89mm 130mm
Weight* 15kg 27kg 44kg 39kg 67kg
Operating temperature** 0...+50°С
Limiting temperature -15...+50°С
IP rating IP22
Mounting horizontal

* Weight w/o installation kit

** At operating temperature +40°С...+50°С operation time in mode Operation from AB will be decreased

UPS and connected AB compatibility

UPS

Connected AB

UPS Marine-1

AB AG-24

UPS Marine-2

AB AG-48

UPS Marine-3

AB AG-72

UPS Marine-5

AB AG-192

UPS Marine-6

AB AG-192

UPS Marine-8

AB AG-240

UPS Marine-10/1

AB AG-240

UPS Marine-10/3

AB AG-240

Technical specifications of PDU / Power distribution unit

Input AC voltage, frequency 50 (60)Hz ± 10Hz, V

main

380 (342 - 418)*; 3 phases

bypass

Rated input current

main

63А per phase

bypass

Connection

main

terminal block

bypass

Output AC voltage, frequency 50 (60)Hz ± 10Hz

 

380V; 3 phases

Rated output current

 

60.6А per phase

Output connectors

 

terminal block - 1 С19** - 2; С13** - 4

Max. load

 

13.3 kW per phase

Parallel port (communication interface)

 

2°С (DB9)

Operating temperature

 

0...+50°С

Limiting temperature

 

-15...+50°С

IP rating

 

IP22

Outline dimensions (WхH)

 

440х725х130mm

Weight***

 

17kg

* Input voltage range

** Reserved pins, not used

*** Weight w/o installation kit

Technical specifications of OPD / Overvoltage protective device

 

OPD-1/1

OPD-2/1

Max. operating current of input voltage

10А

16А

Connectors, pcs.

input

С14 - 1

С20 - 1

output

С13 - 1

С19 - 1

Upper limit of input AC voltage disconnection 50 (60)Hz, V

325 ± 10

Upper limit of AC voltage recovery 50 (60)Hz, V

315 ± 10

Lower limit of AC input voltage disconnection 50 (60)Hz, V

55 ± 10

Lower limit of AC input voltage recovery 50 (60)Hz, V

65 ± 10

Output AC voltage 50 (60)Hz, V

the same as input

Max. operating current of output voltage, А

the same as input

Operating temperature

0...+50°С

Limiting temperature

-15...+50°С

IP rating

IP22

Outline dimensions (DхH)

290х75х44mm

Weight*

1.1 kg

1.2 kg

* Weight w/o installation kit

Technical specifications of SBU / Service bypass unit

 

SBU-1/1-О

SBU-2/1-О

SBU-3/1-О

SBU-3/1-П

SBU-4/3-О

Input AC voltage, frequency 50 (60)Hz ± 10Hz, V

 

220 (180 - 264)*

1 phase

 

380 (342 - 418)*

3 phases

Output AC voltage, V

SBU ON: translation of voltage preset in the SBU settings Manual bypass mode: translation of mains voltage

 

Output frequency, Hz

SBU ON, frequency conversion mode ON: translation of voltage

preset in the SBU settings

SBU ON, frequency conversion mode OFF: translation of mains frequency Manual bypass mode: translation of mains frequency

 

Outline dimensions 

width

270mm

270mm

440mm

440mm

440mm

depth

75mm

75mm

120mm

120mm

725mm

height

88mm

88mm

88mm

130mm

130mm

Weight**

1.3kg

1.4kg

3.5kg

6.2kg

4kg

Operating temperature

0...+50°С

0...+50°С

0...+50°С

0...+50°С

0...+50°С

Limiting temperature

-15...+50°С

-15...+50°С

-15...+50°С

-15...+50°С

-15...+50°С

IP rating

IP22

IP22

IP22

IP22

IP22

* Input voltage range

** Weight w/o installation kit

Downloads